高斌, 李国斌. 中亚天然气管道首站进出站ESD截断阀异常关断分析与技术改造[J]. 油气储运, 2015, 34(10): 1099-1102. DOI: 10.6047/j.issn.1000-8241.2015.10.016
引用本文: 高斌, 李国斌. 中亚天然气管道首站进出站ESD截断阀异常关断分析与技术改造[J]. 油气储运, 2015, 34(10): 1099-1102. DOI: 10.6047/j.issn.1000-8241.2015.10.016
GAO Bin, LI Guobin. Abnormal shutdown analysis and technical transformation of ESD block valve - A case study of initial compressor station of Trans-Asia Gas Pipeline[J]. Oil & Gas Storage and Transportation, 2015, 34(10): 1099-1102. DOI: 10.6047/j.issn.1000-8241.2015.10.016
Citation: GAO Bin, LI Guobin. Abnormal shutdown analysis and technical transformation of ESD block valve - A case study of initial compressor station of Trans-Asia Gas Pipeline[J]. Oil & Gas Storage and Transportation, 2015, 34(10): 1099-1102. DOI: 10.6047/j.issn.1000-8241.2015.10.016

中亚天然气管道首站进出站ESD截断阀异常关断分析与技术改造

Abnormal shutdown analysis and technical transformation of ESD block valve - A case study of initial compressor station of Trans-Asia Gas Pipeline

  • 摘要: 中亚天然气管道首站曾发生进出站ESD截断阀异常关断事件,在现场检查时发现SHAFER气液联动执行机构的消声器不停向外喷射液压油,另外在对站场ESD进行复位时发现进出站ESD截断阀异常自动打开问题。通过全面排查,发现远程ESD机柜受高温天气影响而使机柜内控制模块工作温度超限,导致ESD阀异常关断,而ESD控制逻辑缺陷和SHAFER执行机构ESD开关触点接触不良是ESD复位时进出站ESD阀自动打开和SHAFER执行机构消声器喷油的根本原因。通过相应的技术改造和缺陷整改,彻底消除了首站异常关断的风险隐患,保障了中亚天然气管道的安全平稳运行。

     

    Abstract: Abnormal shutdown of ESD block valve occurred in the initial compressor station of Trans-Asia Gas Pipeline. At the time of on-site check, it was discovered that the muffler of SHAFER pneumatic-hydraulic actuator ceaselessly sprayed hydraulic oil outward. In addition, at the time of restoration to the ESD, it was found that the ESD block valve automatically opened abnormally. Thorough investigation revealed that the abnormal shutdown of ESD block valve resulted from the transfinite operating temperature of control module in the remote ESD cabinet due to high temperature, whereas the control logic defect of ESD and the poor contact of ESD switch of SHAFER actuator were the primary causes for the automatic open of ESD block valve at the time of ESD restoration and the oil spray of muffler of SHAFER actuator at the time of on-site check. Finally, by means of corresponding technical transformation and defect rectification, the potential risk of abnormal shutdown of ESD block valve in the initial station was completely eliminated, which guarantees the safe and smooth running of Trans-Asia Gas Pipeline.

     

/