马应奎, 王新亮. 立式罐油量手工与自动计量结果的对比[J]. 油气储运, 2013, 32(8): 887-890. DOI: 10.6047/j.issn.1000-8241.2013.08.018
引用本文: 马应奎, 王新亮. 立式罐油量手工与自动计量结果的对比[J]. 油气储运, 2013, 32(8): 887-890. DOI: 10.6047/j.issn.1000-8241.2013.08.018
Ma Yingkui, Wang Xinliang. Comparison of manual vs automatic metering readings for oil volume of vertical tank[J]. Oil & Gas Storage and Transportation, 2013, 32(8): 887-890. DOI: 10.6047/j.issn.1000-8241.2013.08.018
Citation: Ma Yingkui, Wang Xinliang. Comparison of manual vs automatic metering readings for oil volume of vertical tank[J]. Oil & Gas Storage and Transportation, 2013, 32(8): 887-890. DOI: 10.6047/j.issn.1000-8241.2013.08.018

立式罐油量手工与自动计量结果的对比

Comparison of manual vs automatic metering readings for oil volume of vertical tank

  • 摘要: 对两座5×104 m3立式金属罐(1201罐和1202罐)分别进行5次高低液位的手工计量与自动计量,并比较二者的油量计算结果。采用数理统计假设检验的方法对结果进行差异显著性判定,对影响计量结果的油高和油温分别进行对比。结果表明:在95%置信水平下,1201罐两种计量方式下的油高差异不显著,平均差异仅1 mm,油温差异显著,平均差异为-0.54 ℃,油量差值范围为2.814~29.225 m3,结果不存在统计意义上的显著差异;1202罐两种计量方式下的油高差异较显著,平均差异为27 mm,油温差异不显著,平均差异为-0.62 ℃,油量差值范围为36.172~97.017 m3,存在显著差异。在国家储罐自动计量标准尚未发布的情况下,可以通过手工计量对比自动计量结果,判定不同计量方式是否存在显著差异,检验自动计量结果的准确性。

     

    Abstract: Five-time manual metering and automatic metering operations on the high/low levels for two vertical metal tanks (5×104 m3), Tank 1201 and 1202, have been carried out and the calculated oil volumes have been compared. Statistical hypothesis testing method is adopted to determine the significant difference of the compared readings so as to separately compare the influencing factors on the metering readings, oil level and oil temperature. Results show that at a 95% confidence level, measured readings from Tank 1201 with the two metering methods have a small difference in oil level data, (only 1 mm on average error), an evident difference in oil temperature data (-0.54 ℃ on average error) and oil volume difference within a range of 2.814~29.225 m3, indicative of no significant differences statistically. While Tank 1201 has an obvious oil level difference (27 mm on average error), a small oil temperature difference (-0.62 ℃ on average error) and an oil volume difference within a range of 36.172~97.017 m3, suggesting significant differences. Since the national automatic metering standards for storage tank are still absent, it can be used to judge whether the measured readings using the two different metering methods have significant differences, and verify the accuracy of automatic metering readings by means of comparing manual vs automatic metering readings.

     

/